Engineering WirelessHART Fieldgate SWG70
66 Endress + Hauser
Procedure for FieldCare In addition to the previous method, in FieldCare the instrument list can also be generated by
importing a network tree created in off-line mode.
1. Create a FieldCare project. See Chapter 7.3.1 "Adding the HART IP CommDTM" on
page 37 and see Chapter 7.3.2 "Adding the Fieldgate SWG70" on page 38
– Put the HART Communication IP CommDTM and Fieldgate SWG70 CommDTM
online.
2. Instead of scanning for devices use the Add Device context menu to add first an
adapter, then the device or devices attached to it.
– For WirelessHART devices without an adapter, just add the device.
3. Repeat Step 2 until the network is complete.
– Edit the long tags so that they correspond to those stored in your devices.
4. Click on Offline Parameterize => Engineering => Instrument List, to display the
empty instrument list.
– You may have to enable the Engineering menu first.
5. Press Import Project Tree to import the network tree.
6. Press Export CSV to store the instrument list on your computer.
7. Close the Offline Parameterize dialog and open the Online Parameterize dialog.
– Click on Engineering => Instrument List to display the empty instrument list.
8. Press Import CSV and import the file you have just created.
9. Press Apply to download the instrument list to the Fieldgate.
10. When the devices join the network at a later time, they will be assigned to their allotted
positions in the Operating Modes list.
11. When all devices have joined the network, return to the Instrument List and press
Refresh to import the latest list.
12. Press Export to store a copy of the list on your computer as a CSV file.
– The file can be re-imported into the Instrument List by pressing Import and
navigating to the folder containing the file.