69
IOM, VS/VT Models, Rev A Enertech Global
Section 12: Troubleshooting
Discharge Suction Subcooling Superheat Water Temp Drop Air Temp Rise
°F GPM/Ton PSIG PSIG °F °F °F °F - DB
1.5 238-368 59-79 7-43 6-24 6-12 12-31
3 246-370 66-87 7-38 4-23 3-7 13-33
1.5 262-384 87-110 6-34 4-20 9-15 17-38
3 271-386 97-122 6-29 4-20 5-9 18-41
1.5 291-413 120-147 6-29 5-20 12-20 21-46
3 301-416 132-162 6-23 7-21 6-11 22-49
1.5 321-447 155-186 4-20 4-25 15-24 24-54
3 332-459 171-210 3-20 8-27 8-13 26-58
Discharge Suction Subcooling Superheat Water Temp Rise Air Temp Drop
°F GPM/Ton PSIG PSIG °F °F °F °F - DB
1.5 197-249 114-147 18-29 6-29 19-30 16-28
3 171-221 112-147 12-21 7-30 9-15 16-28
1.5 269-329 123-157 18-31 4-22 19-28 15-26
3 239-291 121-154 10-21 5-19 9-14 15-27
1.5 352-427 127-162 16-30 4-20 18-27 14-25
3 313-376 126-159 8-21 4-19 8-13 14-25
1.5 455-547 133-167 15-32 4-20 16-25 12-23
3 406-481 131-165 7-20 5-20 8-12 13-23
Heating data based on 70°F EAT. Cooling data based on 80/67°F EAT.
CFM is 325-475 CFM/Ton for heating and cooling except for VS006 (260-340 CFM for 1/2 Ton).
Cooling - No Hot Water Generation
50
Heating - No Hot Water Generation
30
50
70
90
90
110
70
EWT Flow
EWT Flow
Model VS Operating Parameter Tables