31
GB
P 6
Level 0 fan off
Level 1
Level 2
Level 3
2
2
0
This control unit provides you the possibility
to switch a ventilation fan (max. 100 W) and
to set its speed in 3 stages.
The default setting is „no fan“ mode. Only in
afterheating operation after the humid mode
the fan is switched at the maximum speed.
To adjust the fan function please press
„Mode“ button.
The press the „
„ button to reach the fan
symbol and „P6“ in the display.
Please conrm with the „Mode“ button.
Please choose the desired value with the „
“ and „ “ buttons.
They mean:
0 = fan off
1 = fan level 1 (approx. 1/3 output)
2 = fan level 2 (approx. 2/3 output)
3 = maximum fan output
Please confirm with a long press on the
„Mode“ button until the new value is ashing
on the display.
Afterwards the displays shows „P6“ for short
time. Fan function is now stored with the new
value.
The selected level can be seen by the points
under the fan icon on the screen.
P6 Fan operation programming