EasyManua.ls Logo

Esser FACP 8000C - Esserbus Transponder Technical Data

Default Icon
169 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Page 136
Fire Alarm Computer 8000C
23.12 esserbus
®
transponder eK-12-REL
12 freely programmable, potential-free relays, either NC contact or NO contact
Switching power : < 30 V DC/ 1A per relay
External switching voltage,
capable of being monitored : 12 V DC or 24 V DC
23.13 esserbus
®
- transponder eK-32AE
32 freely programmable outputs for activating light-emitting diodes (LED), such as in a remote
indicating panel.
Switching power : 12 V DC / 10 mA per output
External switching voltage,
capable of being monitored : 12 V DC
Lamp test function for checking the indicator LED
23.14 esserbus
®
- transponder eK-1GRP
1 input for connecting a non-addressable fire detector zone
External voltage supply : 10,5 V DC to 28 V DC
Rated voltage : 12 V DC or 24 V DC
Power consumption : max. 28 mA
Detector zones voltage : 9 V DC
Line length in detector zone : max 1000m
External switching voltage,
capable of being monitored : 12 V DC or 24 V DC
Technical Data