Page 98
Fire Alarm Computer 8000C
11 Technical Data
Mains voltage : 230 V AC / 50 bis 60 Hz
Current for external users : max. 2A
Permissible current consumption
with 2 x 24 Ah batteries and 72
hour emergency power supply
: max. 650 mA
Power consumption : max. 100 VA, depending on control panel configuration
Battery charge voltage
Over-discharging protection
:
:
13.9 V DC , at 25 °C ambient temperature
9.5 V DC,
switch-off threshold activation by means of jumper
Protection class :
I
VdS approval : G 296006
Basic module
Capability of operating after CPU
failure
: yes, supply via +5V DCinternal
TTY interface : 20 mA, max. cable length 1000m
Common trouble relay : contact rating max. 30 V DC / 1A
Quiescent current : 150 mA (incl. operating panel card and power supply)
Field device module
One micromodule slots with their own 8-pole terminal card.
Quiescent current : ca. 10 mA (without micromodule)
Technical Data