Fire Alarm-Computer 8000C Pag
e 143
25 Installer level
Operations and fire alarm control panel functions which should only be performed by specialised
installers or authorised persons are integrated under the menu point
Installer
in the fire alarm
control panel 8000C. The service level is protected from unauthorised access by a numeric
authorisation code. This authorisation code is dependent on the
country function
programmed in
the customer data.
The menu point
Installer
is only displayed in the service level!
Pressing the
Installer
function key moved from the service level to the installer level. Before entry
to the installer level, the authorisation code must be entered. (Exception: The requirement of the
authorisation code has been deleted by the programming of the Customer data)
The authorisation for operations in the Installer level remains active until the keyboard cover (key
switch) is closed or no keyboard operation is carried out in the installer level for more than ten
minutes. During this period, access is possible to the various display levels without further
authorisation.
Works programmes authorisation code
Code: 123 for programmes Country functions for (Germany, Great Britain, Switzerland
and others)
20290 for programmed Country function for The Netherlands (NL)
--- for programmed Country function for Austria
(no works programmed authorisation code)
The authorisation code programmed at works level through the MCountry function can be changed
individually in the PC Customer data programming of the FACP 8000C.
Installer code unknown
If the installer code is unknown or has been forgotten, it can be easily queried with the service PC.
For this purpose, the Customer data is obtained from the control panel by the Customer data
editor 8000C. The max. 8-digit authorisation code is then displayed under menu point "
Customer
data - installer code
" . Storage of the Customer data which has only been queried to obtain the
installer code is not necessary.
Commissioning / Servicing