EasyManua.ls Logo

EXFO MaxTester 700 - Page 83

EXFO MaxTester 700
381 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Testing Fibers in Advanced Mode
MAX-700 71
Setting Pass/Fail Thresholds
The following table provides the default, minimum and maximum
thresholds.
Once the thresholds are set, the application will be able to perform
Pass/Fail tests to determine the status of the various events (pass or fail).
The Pass/Fail test is performed on two occasions:
when analyzing or reanalyzing a trace
when you open a trace file
Values that are greater than the predefined thresholds are displayed in
white on a red background in the events table.
The Pass/Fail threshold LED, located on the front of the unit, will also
indicate the status (green for pass, red for fail).
You can also set the application to display pass/fail messages when the
Pass/Fail test is performed.
Test Default Minimum Maximum
Splice loss (dB) 1.000 0.015 5.000
Connector loss (dB) 1.000 0.015 5.000
Fiber section attenuation (dB/km) 0.400 0.000 5.000

Table of Contents

Related product manuals