EasyManua.ls Logo

Festo Compact Performance CP-FB9-E - Operation with General DP Master; Starting the Bus

Festo Compact Performance CP-FB9-E
103 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
2.3 Operation with general DP master
The Festo CP system can be controlled from any PLC,
PC or industrial PC with a PROFIBUS-DP module as
per EN 50170 (DIN 19245).
Information on the functions FREEZE and SYNC, the
DP identifiers, satndard and compact mode can be
found in section 2.1.4.
2.3.1 Starting the bus
In order to operate the CP system correctly, the DP
master must perform the following functions in the se-
quence specified:
1. Send a parametrizing telegram
2. Send a configuration telegram
3. Request diagnostic information
4. Start useful cyclic data transmission
The structure and content of the individual telegrams
are described in subsequent chapters.
2. Commissioning
2-32 CP FB13-E 9904b