EasyManua.ls Logo

Festo MPA-FB-VI - Operating States of the Pneumatic System

Festo MPA-FB-VI
218 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
4. Commissioning
4-22
Festo P .BE-MPA-EN en 1108e
4.7.2 Operating states of the pneumatic system
The following conditions should be fulfilled, in order that the
desired pneumatic operating states listed below can be
achieved:
Desired
pneumatic
operating status
Prerequisites Comment
Zero-leakage Tubing connected with care
Regulated pilot air supply
Fast reaction Sufficient pressure supply b y means
of pressure supply modules
Exhaust the MPA-S valve terminal via
all exhaust plates or flat plate
silencer
Trouble-free Non-return valves in common
exhaust line
This applies when several systems
with centrally ducted exhaust are
used
Two or more
pressure zones
Limiting the pressure zones by
means of isolating seals with
blocked channels
Appropriate number of pneumatic
air supply plates for supplying the
different pressure zones.
Subsequent conversion possible
(see Chapter 5)
Vacuum or
low-pressure
operation
Externally supplied regulated pilot
air supply ( 3 8 bar)
Vacuum/Low pressure operation not
with 2x2/2- and 2x3/2-way valves
(Ident.codeD,I,H,K,N)
EMERGENCY STOP of
pressure zones
Guaranteeing the c ontroller function
for the pilot a ir supply despite the
overall supply being switched off
The controller regulates the pilot air
supply to all the valve plates on an
MPA-S valve terminal
Slow star t-up after
EMERGENCY STOP
If control signals are present, the
pilot air supply must have a pressure
of 3 ... 8 bar immediately after being
switched on
Tab. 4/11: Pneumatic operating states

Table of Contents

Related product manuals