The 3 key shows the panel View log or moves the
panel to the Modify mode.
The 4 key selects between the function groups related
to the keys 1,2,3.
Cursor keys The UP Key increases the brightness of
LCD display.
the Down Key decreases the brightness of LCD dis
-
play.
the Right Key increases the contrast of LCD display.
the Left Key decreases the contrast of LCD display.
ESC Key Exit from the MAIN page, moves the User In
-
terface to FRONT page or EVENT DRIVEN page.
Pressing the key for more than 3 seconds. the panel will
be forced to access Level 1.
ENTER Key No function is related to the ENTER key.
n
Diagnostic pages
These pages allow:
Ø
the display of some electrical parameters inside the
panel (Panel meter page)
Ø
the display of some functional parameters related to
the loops (LOOP page)
Ø
To execute the panel keyboard test (KEYBOARD
TEST page).
These pages are reached during the normal operation
from the Main page after a long pressing key 4.
n MENU page
The MENU pages allow access to the PROGRAM, AN-
ALYZE, DISABLE and MODIFY features of the panel.
The part relating to the User will be explained in the sec-
tions of this manual: ANALYZE, DISABLE and MOD-
IFY. The part relative to the Installer will be explained in
the section PROGRAM in the Installer manual.
n
The EVENT DRIVEN pages
The EVENT DRIVEN pages are activated by events in the
system and when they become active, they override the
page present on the display at that time. An EVENT
DRIVEN page may be overridden by another EVENT
DRIVEN page that has a higher priority.
The following table contains the EVENT DRIVEN page
priority assignment:
The Event Driven pages Priority
ALARM
0 (highest)
DELAY TO ALARM
1
FAULT
2
WARNING
3
WALK TEST
4 (Lowest)
In the case of lower priority Event pages (one or more)
being suppressed by the highest priority Event page,
the MORE INFO LED is ON. In this condition, the
suppressed EVENT pages may be manually reached
using the View list. entry in the MAIN page.
n WARNING STATUS
The FC501 fire control panel can be programmed to
provide WARNINGS or DELAY TO ALARMS status be-
fore ALARM status.
The Warning status will be signalled by the WARNING
display (see Figure 6). The panel will generate a warn-
ing when an input point (detector) exceeds its warning
threshold and there is risk of an alarm.
WARNING STATUS will be signalled by:
Ø
Warning output points;
Ø
fire control panel Display;
Ø
intermittent audible signal on the panel buzzer;
Ø
the FC500REP repeater.
In this phase:
10 Addressable Fire Control Panel FC501
LOOP
A avg=096 , min=090 , max=106
B avg=170 , min=165 , max=192
C count = 0000
Panel meter
V PSU 27.5Vdc I_PSU 325.0mA
Vbatt. 27.4Vdc Batt.Res 200.0mOhm
ESC
MAIN page
ESC
MAIN page
KEYBOARD TEST
[1] [2] [3] [4] [5] [6] [7] [8]
[9] [0] [ENT][ESC][UP] [DWN][LFT][RGH]
[HLP][SIL][EVC][RST][SBZ][INV][LMP]
ESC
MAIN page (Long press)
V-PSU= displays the output voltage of the panel power supply
I-PSU= displays the output current of the panel power supply
If I-PSU<150mA displayed “LOW”; Vbatt=displays the battery voltage.
Batt.Res=Display the value of the battery internal resistance plus the battery
wiring res.
LOOP Diagnostic page
It is a general purpose page used to display, in real time, the values of FW
parameters related to the loop management. The rows labeled A and B
display the average, minimum and maximum value of the FW parameter related to them.
The rows labeled C counts the occurrence of event related to the assigned FW parameter.
Pushing the 0 key all the displayed values are reset.
KEYBOARD TEST
This page allows the test of all key in the panel User Interface Pushing any keys
on the panel User Interface the relevant portion in the display will be blanked
if the key press is sensed.
If Batt.res > 9999mOhm or Vbatt. < 19Vdc displayed ¯NO BATT