DISABLE
To access the DISABLE menu from the MAIN page,
you will be asked to enter a “User PIN” password (the
default PIN is 11111): each entered digit will be hidden
with the * symbol.
This activates the procedure used to enable/disable:
Display List of disabled devices, the loop devices (input
or output devices), the SW zones, the Outputs of the
control panel, the network devices, the Telecom mod
-
ules, the User password and the RELÈ FIRE Output;
+
When a device is disabled, the Disable LED will be
glowing , and any Alarm or Fault, related to the
disabled device, will be ignored.
The disabled and enabled modes are as follows:
Input Devices A disabled input device (Detector, In-
put module, Conventional Zone module, Addressable
Call-points) will not generate ALARM or FAULT status.
Ø To clear ALARM status generated by an input device
- RESET the fire control panel.
Output Devices ALARM or FAULT status will not acti-
vate disabled output devices (Output modules, Ad-
dressable Sirens).
Ø
To stop the output devices activated by FAULT sta
-
tus - Disable the devices concerned.
Ø
To stop the output devices activated by an ALARM
status - RESET the fire control panel.
+
Output devices enabled during ALARM or FAULT
status (programmed), will be activated immedi
-
ately.
The display (see Figure 18) shows how to select the de
-
vices to Disable/Enable.
In this phase:
Alphanumeric keypad Use the Alphanumeric keypad
to select the Disable/Enable options.
Use the 1 key to select the Disab. List.
Use the 2 key to select the Disable option of Loop de
-
vices.
Use the 3 key to select the Disable option of SW zones.
Use the 4 key to select the Disable option of Outputs.
Use the 5 key to select the Disable option of Device in
the Network.
Use the 6 key to select the Disable option of Comunic.
devices.
Use the 7 key to select the Disable option of the User
Password
# 2.... # 8 and Installer # 2.
Use the 8 key to select the Disable option of the FIRE
relay output.
+
The option 7 can be enabled only by the Installer
#1 password (default 00000)
Cursor Keys No function is related to the UP, Down,
Right and Left Keys.
ESC Key Use the ESC key to cancel the operation and
to step back to previous page.
ENTER key No function is related to the ENTER key.
DISABLE 27