Alphanumeric keypad 0 key: if the Warning is related
to an item that may be disabled, the User Interface
moves to the disabling page.The following key func-
tions allow for a fast disablement procedure:
1 key: to jump to the Zone status visualization page;
2 key: if the first Warning is related to a point, jump to
loop device status visualization page;
3 key: if the last Warning is related to a point, jump to
loop device status visualization page;
4 key: to display further Warning.
When a point Warning is present in the fourth row, a fur-
ther 4 key press will cause the User Interface to jump to
the related loop device status visualization page.
From Figure 6, in the WARNING STATUS, use the
RIGHT Key to scroll the second string of data of Warn
-
ing Zones; then use the RIGHT Key to scroll the third
string of data of Warning causes; then use the RIGHT
Key to scroll the fourth string of data of Warning Times
and Events.
+
If the events are linked to the devices, the zone la
-
bel alternates with the point label every 3 seconds.
If the zone has not been associated with the point,
only the point label will appear.
Cursor keys Use the UP Key to view the next event,
other than the first and the last;
Use the DOWN Key to view the previous event, other
than the first and the last.
Use the RIGHT Key to view the next string of data.
Use the LEFT Key to view the previous string of data.
ESC Key Use ESC key to cancel the operation and to
step back to MAIN page.
ENTER Key The ENTER Key blocks/reactivates the ex
-
change between the labels of the devices and those of the
zones. When the block is enabled, the @ character ap
-
pears in the top left-hand corner of the display.
n Delay to Alarm STATUS
This status indicates that an input point (detector) has
exceeded its alarm threshold. The fire control panel will
not generate an alarm until the preset delay to alarm-
time ends. However, if a second input point (detector in
the same SW zone) detects alarm conditions during the
Delay to Alarm phase (and the “Double knock” option
has been programmed for that zone), the fire control
panel will generate an instant alarm.
If the fire control panel is operating in NIGHT mode, it
will generate INSTANT ALARMS ONLY (Delay to
Alarm status will be bypassed automatically). If an
alarm procedure is already running, the fire control
panel will ignore delay to alarm conditions.
USER INTERFACE 11
Total :0015 status:WARNING
First : zone: R-D department EVAC.
Last : zone=456zone: Air compressor n1
#0011 : zone=245zone: Boiler room
Push the right key to scroll
the second block of data
regarding the WARNING zones
Total :0015 status:WARNING
First : MS:Loop 1 mod012 zone=067
Last : MS:Loop 1 mod182 zone=456
#0011 : MS:Loop 2 det034 zone=245
Total :0015 status:WARNING
First : cause: EVAC.
Last : cause: CP820 Manual
#0011 : cause: 801PH Temp.
Total :0015 status:WARNING
First : Time: 10:46:21 - 01/01/07
Last : Time: 10:47:18 - 01/01/07
#0011 : Time: 10:47:12 - 01/01/07
Push the right key to scroll
the third block of data
regarding the WARNING causes
Push the right key to scroll
the fourth block of data
regarding the WARNING times
Figure 8 Warning status - Scrolling Right key.
Zones:004 / Dev.: 013 ALARM+DLY
First Z001 det.: office 3, south wing
Last Z001 det.: main corridor, north
4= view all
Zones:004 / Dev.: 013 ALARM+DLY
First Z001 Loop 1 mod012 zone=001
Last Z001 Loop 1 mod182 zone=001
4= view all
ALARM+DLYZones:004 / Dev.: 013
First cause: 400PH Temp.Z001
Last cause: 400PH Temp.Z001
4= view all
Zones:004 / Dev.: 013 ALARM+DLY
First Time: 10:46:21 - 01/01/07Z001
Last Time: 10:47:18 - 01/01/07Z001
4= view all
Push the right key to scroll
the second block of data
regarding the Points Coordinate
Push the right key to scroll
the third block of data
regarding the PREALARM causes
Push the right key to scroll
the fourth block of data
regarding the PREALARM times
Push the left key
Push the left key
Push the left key
Figure 9 Delay to alarm status - Scrolling Right key.
zones:004 / Dev:013 ALARM+DLY
First z001 det: office 3, first floor
Last z004 det: main corridor
4= : view suppressed Delay to alarm
Blinking
Points in Prealarm counter
To view further points
in Prealarm
Last point in
Prealarm
Control panel status
First Point in
Prealarm
This symbol
the presence of following
information: point coordinate
Cause
Time
shows
BY POINTS
Point label
swapped with
zone label
30 sec. or
zones:004 / Dev:013 ALARM+DLY
First z001 zone: RD dept. first floor
Last z004 zone: Warehouse
4= : view suppressed Delay to alarm
Blinking
Zones in Prealarm counter
To view further zones
in Prealarm
Last zone in
Prealarm
Control panel status
First zone in Prealarm
If blinks
indicates the
control panel
operating normal
BY ZONE
Zone label
swapped with
point label
This symbol
the presence of following
information: point coordinate
Cause
Time
shows
Figure 10 Display: DELAY TO ALARM STATUS.