1 KEY - View Loop
Use the 1 Key to view the Loop data (see Figure 17).
n
View of Loop Details
In this phase:
Alphanumeric keypad No function is related to Al
-
phanumeric keypad.
Cursor Keys Use the UP Key to select the next Loop
data;
Use the Down Key to select the previous Loop data;
No function is related to the Right Key;
No function is related to the Left Key.
ESC Key Use ESC key to step back to previous page.
ENTER Key No function is related to the ENTER key.
In the Figure 19, the “loop=” field shows which loop de
-
tail is displayed.
The “Detectors:” field displays the number of detectors
sensed on the relevant loop.
The “Modules:” field displays the number of modules
sensed on the relevant loop.
The “Status:” field displays the status of the selected
loop. The possible values are:
Ø Working,
Ø Fault,
Ø Stand_by,
Ø Disabled.
The “loop=” field real time display (5 seconds data re-
fresh rate) the total current supplied to all three loops.
2 KEY - View Devices
Use the 2 Key to view the Loop devices (see Figure 18).
In this page: Select the Loop and then the device.
n
Select the Loop
In this phase:
Alphanumeric keypad 1,2,3 used to select the loop.
Cursor Keys No function is related to UP Key;
No function is related to the Down Key;
Use the Right Key to select the next available Loop;
Use the Left Key to select the previous available Loop.
ESC Key Use the ESC key to cancel the operation and
to step back to previous page.
ENTER key Use the ENTER key to confirm and to dis
-
play the page of the selected Loop.
n
Select the device
After selecting the Loop, the Loop details are shown as
in Figure 20.
In this phase:
Alphanumeric keypad Use the Alphanumeric keypad
to insert the device address. If the address does not ex-
ist the next available device will be selected.
+
If the device is in the system, the square brackets
will be shown near the address. If the address does
not exist or it is different from that selected in the
underlying bar, the arrows will be shown.
Cursor Keys No function is related to the UP Key;
No function is related to the Down Key;
Use the Right Key to select the next available Device;
Use the Left Key to select the previous available device.
ESC Key Use the ESC key to cancel the operation and
to step back to previous page.
ENTER key Use the ENTER key to confirm and to dis
-
play the page of the selected device.
16 Addressable Fire Control Panel FC501
Loop= 01 lev.1: ANALYZE
Modules : 125
Status: Working
Loop number
ILoop=073 mA (400 ma MAX)
Current Value
in the 3 Loops
Present Status
of the Loop
Detectors: 125
Detectors Number
Modules
number
Overcurrent that
powers OFF the Loop
If it blinks the panel
is operating normally
Figure 19 DISPLAY: Viewing Loop details.
FC501 Panel lev.1: ANALYZE
Master Panel
[L1] L2
Control panel name
Access level
Choose Panel Loop 1
Initial of the selected
Control panel Loop
Name of the
Control panel
If it blinks the panel
is operating normally
Control panel status
Figure 18 Display: viewing a) Loop choice, b) Loop de
-
tails.