3 KEY- View SW Zone
The 3 Key (SW Zone) option in the ANALYZE menu ac
-
tivates the viewing of the software zones (max 32). Dur
-
ing this phase (see Figure 21) the status of all the SW
zones in the system is displayed in compact format. The
status of the SW zones will be displayed using the fol
-
lowing abbreviations:
. : “UNUSED” Not used zone, no devices assigned to it
A: “ALARM” zone in Alarm mode
P: “PRE AL.” zone in Delay to alarm mode
W: “WARNING” zone in Warning mode
F: “FAULT” zone in Fault mode
X: “DISABLED” zone Disabled
t: “TEST” zone in Test mode
T: “TEST ON” At least one point in the zone is active in
test
_: “ST-BY” zone in standby mode
D: “DIRTY” At least one smoke detector in the zone is
dirty.
Alphanumeric keypad No function is related to Al
-
phanumeric keypad.
Cursor Keys No function is related to UP key.
No function is related to the Down key;
the Right Key: selects the next SW zone, in the “All
zone status area”;
(the corresponding number appears on the Left of the
display);
the Left Key: selects the previous SW zone, in the “All
zone status area”;
(the corresponding number appears on the Left of the
display).
ESC Key Use ESC key to cancel the operation and to
step back to previous page.
ENTER key No function is related to ENTER key.
4 KEY- View Output
The 4 key Output option in the ANALYZE menu acti
-
vates the viewing of the Outputs. During this phase (see
Figure 22) the status of all the Outputs in the system is
displayed in compact format. The status of the Outputs
will be displayed using the following abbreviations:
-DIS: output disabled
-ACT: output active
-SC: output shorted
-OPE: output open
-_ _ : output in standby
-FAU: transistor Fault
Alphanumeric keypad No function is related to Al
-
phanumeric keypad.
Cursor Keys No function is related to the UP, Down,
Right and Left key.
ESC Key Use the ESC key to cancel the operation and
to step back to previous page.
ENTER key No function is related to the ENTER key.
18 Addressable Fire Control Panel FC501