This Fire Control panel can be programmed only using
the Software FireClass Console release 1.0 or higher.
Control panel FW ver. 1.0 or higher.
TYCO shall not assume the responsibility for damage
arising from improper application or use. This Control
panel has been designed and manufactured to the
highest standards of quality and performance. Installa
-
tion of this Control panel must be carried out strictly in
accordance with the instructions described in this man
-
ual, and in compliance with the local laws and bylaws in
force.
The FC501-L, FC501-H and FC501-HK Fire Control
panels comply with the essential requirements of stan
-
dards EN54-2: 1997+A1:2006; EN54-4:
1997+A1:2002+A2:2006; EN 54-21.
The manufacturer reserves the right to change the tech
-
nical specifications of these products without prior no
-
tice.
Recycling information
The manufacturer recommends that customers dis
-
pose of their used equipment (panels, detectors, sirens,
and other devices) in an environmentally sound man
-
ner. Potential methods include reuse of parts or whole
products and recycling of products, components,
and/or materials.
Waste Electrical and Electronic Equipment (WEEE)
Directive
In the European Union, this label indicates that
this product should NOT be disposed of with household
waste. It should be deposited at an appropriate facility
to enable recovery and recycling.
NOTE- The FC501-L, FC501-H and FC501-HK control
panel can support several addressable devices (Detectors,
Modules, Manual call Points, etc). The present manual in
-
cludes the instructions for their programming, but for further
information on those devices and their accessories, please
visits: www.fireclass.net.
Maintenance
To ensure that the system continues to operate nor
-
mally it must be maintained with regular testing by the
user and periodic maintenance by the installer in accor
-
dance with local laws.
+
For the maintenance of other devices such as de
-
tectors, modules, etc. follow the dedicated instruc
-
tions for the devices.
The following operations must be carried out regularly.
A Using a damp cloth (DO NOT USE SOLVENTS OF
ANY KIND), remove dust from the Control panel cabi
-
net.
B Using the Lamp Test key, check that the LEDs and
buzzer are functioning properly.
C Ensure that the batteries are sufficiently charged and
functioning properly. If not, replace them immediately.
D Ensure that all cables and connections are intact.
E Ensure that there are no unrelated objects inside the
Control panel case.
F Ensure that the control panel is capable of process-
ing a fire alarm and if a siren (sounder) is present in the
system, it is activated in consequence of this alarm. If
there is a facility for transmission of fire alarm signals to
a Central Station, it should also be ensured that the sig-
nal is correctly received.
G Also verify the actual functionality of the circuit for the
detection of earth fault. The procedure is as follows:
Ø connect one of the SH terminals of the loop to the
panel ground (earth);
Ø
verify that the fault is reported correctly by the Fire
Panel;
Ø
remove the connection previously made.
Points A and B may be carried out by users.
Points C, D, E, F and G must be carried out by qualified
persons only.