8 Addressable Fire Control Panel FC501
LED ICON DESCRIPTION
FIRE
(Red)
Glowing indicates Alarm status. In the event of an Alarm, the Control panel will activate the
unbypassed alarm outputs.
SOFTWARE
ZONES
(Red) (1-8)
-
Glowing indicates that the corresponding Software zone is in Alarm status (*).
Slow Blinking indicates that the corresponding Software zone is in Delay to Alarm status.
OFF indicates no alarms, The zone is in stand-by status.
FIRE SIGNAL
ON (Red)
Glowing indicates that transmission was successful.
Slow Blinking indicates that transmission is in progress. On the display of the control pa
-
nel it is possible to know the connection type: PSTN, GSM, or LAN network.
OFF indicates the communicator is in stand-by status.
GENERAL
FAULT
(Amber)
Glowing indicates the presence of a Fault: the following LEDs or the screen on the display
indicates the type of the Fault.
Slow blinking indicates a fault event in memory (Reset turns OFF ).
OFF indicates no Fault.
SYSTEM
FAULT
(Amber)
Glowing (**) indicates a blocked Control Panel. IMPORTANT: Maintenance required.
Slow blinking (***)indicates the Control Panel restart.
Fast blinking (***) indicates that the panel programming data is corrupted.
NOTE When the Control panel is switched on for the first time, this LED will blink until a
Reset has been performed.
FIRE SIGNAL
FAULT
(Amber)
Glowing indicates the communicator has been disabled.
Slow blinking indicates that the communicator has broken down.
OFF indicates no fault relative to communicator.
SOUNDERS
FAULTS/DIS
Glowing indicates that SC 1 Output is disabled or SC2 "act as SC1" is disabled.
Slow blinking indicates that SC1 is in fault or SC2 "act as SC1" is in fault.
OFF indicates all the SC outputs function properly.
EARTH
FAULT
(Amber
Glowing indicates a Voltage leakage to Earth.
IMPORTANT: Check wiring insulation.
OFF indicates no Earth faults are present.
BATTERY
TROUBLE
(Amber)
Glowing indicates Batteries empty or faulty. If this condition persists, the batteries will be un-
able to function as intended in the event of blackout. IMPORTANT: New batteries required.
Slow blinking indicates a fault event in memory (Reset turns OFF ).
OFF indicates the batteries are healthy.
POWER
SUPPLY
FAULT
(Amber)
Glowing indicates Mains failure.
Fast blinking indicates Switching Power supply fault.
During this condition, the Control panel will be powered by the batteries.
OFF indicates the presence of the Main and the power supply functions properly.
DAY MODE Glowing indicates that the Control panel is operating in DAY MODE.
OFF indicates that the Control panel is operating in NIGHT MODE.
DISABLED Glowing indicates the Disabled status of any bypassable entity.
OFF indicates no entity is disabled.
SOUNDERS
SILENCED
(Amber)
Glowing indicates that Silenceable outputs and Loop devices have been forced to
standby by means of SOUNDER SILENCED key; in Day Mode the SILENCE will remain
until the SILENCE key is pressed again, while in Night Mode after the Silence Time expi
-
res automatically the SILENCE will end.
Test Glowing indicates Test conditions on at least one zone.
OFF indicates no zone is in Test.
MORE INFO
(Amber)
Glowing indicates that there is hidden information with lower priority: access to the page
View List to show the hidden information.
OFF indicates no hidden information is presents.
CONTROLS
ON (AMBER)
-
Glowing indicates that the Control Panel is at least at level 2 so the Silence/Resound So
-
unders, Reset and Investigation Delay Keys are enabled.
POWER ON
(Green)
Glowing indicates panel is supplied with power.
OFF indicates Mains failure (both mains & battery power is lost) (Battery disconnect
threshold: 19,2 V). Mains Power must be restored before the batteries reach the discon
-
nect threshold.
Table 2 Description of the status LEDs. (*) the zone outside this range (1 to 8) does not have a related LED, its alarm
status is displayed only by the LCD, (**)buzzer SYSTEM FAULT pattern, (***)buzzer FAULT pattern,
These icons are not shown on the UK User Interface panel.