4.16 Inspection prior to commissioning, maintenance and re-inspection
They guarantee operational safety and its observance in line with applicable European regulations, European
and harmonised standards and additional national regulations of the EU member states for this field
of application. The required inspections must be arranged by the owner or operator; an inspection and
maintenance log book for scheduling and traceability of measures taken must be kept.
Tests in line with the German ordinance on operational safety (BetrSichV, June 2015):
Pressure equipment, vessels (§14; 15)
Category [see
appendix II
of Directive
2014/68/EU,
diagram 2)
Nominal vessel
capacity
[litres]
Inspection
prior to
commis-
sioning [§14]
inspector
Re-inspection [§15 (5)]
Timeframe, maximum period [a] / inspector
External inspection Internal inspection Strength inspection
II 200- 300 / 3 bar Qualified Person
(QP)
Maximum period not defined. The maximum interval must be established by the Operator on the basis
of information provided by the manufacturer coupled with practical experience and chamber load. The
inspection may be carried out by a Qualified person.
III 400- 10000 / 3 bar No longer applicable [§15 (6)] 5 / QP 10 / QP
[§15 (10)] In the case of internal inspections the visual inspection
may be replaced by similar procedures and in the case of strength
tests the static pressure test may be replaced by similar, non-
destructive procedures if said tests would not otherwise be possible
due to system design or not significant due to the system mode of
operation.
Maintenance of equipment, interior and strength inspection, see maintenance, Ch. 8.
In other Member States of the EC, the required tests for the pressure equipment in line with directive 2014/68/EU
as defined in the national rules must be performed.
4.17 Electrical equipment inspections, routine inspection
Without prejudice to the considerations of the insurer/Operator, it is recommended that the electrical equipment
of the Flamcomat be inspected and documented together with the heating/cooling unit no less than every 18
months (see also DIN EN 60204-1 2007).