Manual Flamcomat G4 + Flamcomat Starter G4
We reserve the right to change designs and technical specifications of our products.
33
ENG
Lorem ipsum
dolor sit
Operation screen Menu screen Settings screen Read only screen
Operation Screen
Lorem ipsum
dolor sit
2.2 bar 12 %
1
2 3 4
1
6
7
5
8 910
1
Screen icon
2
Node number
3
Logged in
4
Current System Pressure
5
Current vessel level
6
Refill
7
System
8
Valve(s)
9
Pump(s)
10
Vessel
- bubbles indicates degassing on/o
- animated bubbles indicate degassing active
- arrow indicates increase/decrease o water level in expansion
vessel
Pressure settings
5
4
3
2
1
2.2 bar 12 %
High pressure alarm 6,0 bar
Pset+ 2,2 bar
Pset 2,0 bar
Pset – 1,8 bar
Low pressure alarm 0,6 bar
1
High pressure alarm
2
Upper operating pressure tollerance
3
Operating pressure
4
Lower operating pressure tollerance
5
Low pressure alarm
Degassing settings
2.2 bar 12 %
STANDARD
Exclusion of time
Residential
FAST
Hotel
Hospital
OFF
Oice
1
2
3
8
7
6
5
4
Main de-aeration function
1
Degassing mode normal
2
Degassing mode Turbo (24h of high frequency degassing)
3
Degassing mode OFF
Sleep interval settings of de-aeration function.
4
No silent hours profile active
5
Degassing possible on weekdays from 9.00 to 17.00
6
Degassing possible every day from 10.00 to 17.00
7
Degassing possible everyday from 9.00 to 21.00
8
Degassing possible on weekdays and saturdays from 19.00 to
7.00 and Sunday
2.2 bar 12 % 2.2 bar 12 % 2.2 bar 12 % 2.2 bar 12 %
Settings Log in
High pressure alarm 6,0 bar
Maintenance 1 11-11-2018
Maintenance 2 11-11-2018
Pset + 2,2 bar
Maintenance 3 11-11-2018
Pset 2,0 bar
Maintenance 4 11-11-2018
Manual mode Service Info
Pset - 1,8 bar
Low pressure alarm 0,6 bar