Error #
GUI Action
17
Maximum run time M1 exceeded The pump runs too long. Please make sure there is no leakage in the system
18
Maximum run time M2 exceeded The pump runs too long. Please make sure there is no leakage in the system
19
Maximum supplation threaded water amount exceeded Please replace a filter
20
Pump running, no decrease of water level in vessel Potential failure of pump(s) or clogged vessel drain tube
21
Valve open, no increase of water level in vessel Potential failure of valve(s) or clogged vessel supply tube
22
Maximum run time V1 exceeded The valve runs too long. Please make sure that the balancing valve settings is
correct
23
Maximum run time V2 exceeded The valve runs too long. Please make sure that the balancing valve settings is
correct
24
To run quick fill Acknowledge error in current errors/warnings to run Quick fill
25
To run system fill Acknowledge error in current errors/warnings to run System fill
26
System run in auto mode You have le the manual mode. Automat maintains the pressure
27
Quick system filling active, V to stop Press V to stop/pause Quick System fill
28
System filling active, V to stop Press V to stop/pause System fill
29
Manual mode active, press V to start automat Acknowledge this message to run the automat in the AUTO mode (to leave the
MANUAL mode)
30
Diaphragm rupture The membrane is ruptured and should be replaced
32
Water level increase in vessel without Flamcomat activity Potential failure of manifold-, refill- or check valve
33
Water level decrease in vessel without Flamcomat activity Potential leakage of vessel or connection sets, or failure of drain valve
34
Maintenance is due 1 Carry out maintainance 1 (equipment service, every 1 year)
35
Initial fill failed Potential failure of refill valve or clogged supply tube
36
Maximum refill time exceeded Potential failure of refill valve
37
Maximum drain time exceeded Potential failure of drain valve
38
No refill flow Please make sure the liter counter is available
39
Amount refill water too much System requires to much refill. Potential leakage
43
Initial fill active The automat fills a vessel with minimum amount of water
44
Manual initial fill active Fill in a vessel with minimum amount of water
45
System fill timer expired System fill took too long. Please check the system and restart the filling process
46
Quick fill timer expired System fill took too long. Please check the system and restart the filling process
47
Maintenance is due 2 Carry out maintenance 2 (inspect vessel internally, every 5 years)
48
Maintenance is due 3 Carry out maintenance 3 (strength inspection to vessel, every 10 years)
49
Maintenance is due 4 Carry out maintenance 4 (inspect electrical equipment, every 1,5 years)
64
Low pressure alarm System pressure is lower than "Low Pressure Alarm"
65
Higher pressure exceeded System pressure is higher than "High Pressure Alarm"
66
Water Level below minimum value Water level in a vessel is lower than "Low level limit"
67
Water Level above maximum value Water level in a vessel is higher than "High level limit"
68
Pressure below minimum value The risk of a steam formation. Turn o a boiler
69
Dry run protection The refill pump cannot start as it is dry
70
Critical Water Level Water level in a vessel is lower than "Minimal level limit"
72
Temperature too high The temperature on the automat inlet is higher than 70°C. Please use an
intermediate vessel
73
Time between refill processes too short System requires to much refill. Potential leakage
74
Number of refills within certain time exceeded System requires to much refill. Potential leakage
75