Basic Cabling Testing
Permanent Link Connections
7
7-7
Permanent Link Connections
Permanent link test connections are similar to basic link connections, except that
the effects of the test equipments patch cables are excluded from the test results.
When compared to the basic link and channel, this test configuration provides the
most accurate characterization of the permanently installed section of the cabling.
The permanent link configuration also helps eliminate false FAIL results caused
by test equipment patch cables. Figure 7-6 illustrates permanent link test
connections.
Test equipment
patch cable
Test equipment
patch cable
Horizontal cabling
Permanent link
Patch panel
connection
Test Tool
Smart
Remote
TALK
Start permanent
link
End permanent
link
Consolidation
point (optional)
oy87f.eps
Figure 7-6. Permanent Link Test Connections