Agency Approvals
CE: Approved
EMC Directive; 2014/30/EU
Electrical Equipment for Measurement, Control and Lab Use: EN61326-1:2013
Low Voltage Directive (LVD): 2014/35/EU
Product Safety Testing: EN 61010-1: 2010
Pressure Equipment Directive: 2014/68/EU
Weld Testing: EN ISO 15614-1 and EN ISO 9606-1, ASME B31.3
FM and FMc: Approved
Class I, Division 1, Groups B,C,D;
Class II, Division 1, Groups E,F,G;
Class III, Division 1; T3C, Ta = - 40˚C to +70˚C;
Class 1, Zone 1, AEx/Ex d IIB + H2 (T6, T4, or T1*); Ta= -20˚C to +70˚C; Type 4X (IP67)
ATEX (FM12ATEX0034X): Approved
II 2 G Ex db IIB + H2 (T6, T4, or T1*) Gb Ta = - 20˚C to +70˚C; IP67
II 2 D Ex tb IIIC (T85˚C, T135˚C, or T450˚C*) Db Ta = - 20˚C to +70˚C; IP67
IECEx (IECEx FMG 12.0010X): Approved
Ex db IIB + H2 (T6, T4, or T1*) Gb Ta = - 20˚C to +70˚C; IP67
Ex tb IIIC (T85˚C or T135˚C*) Db Ta = - 20˚C to +70˚C; IP67**
ATEX and IECEx Standards:
EN 60079-0 EN 60079-31 IEC 60079-0 IEC 60079-31
EN 60079-1 EN 60529 +A1 IEC 60079-1 IEC 60529
Model Code Temp. Code Marking - Zones (Gas) Temp. Code Marking - Zones (Dust)
Enclosure Sensor Type Main Enclosure Remote Enclosure Main Enclosure Remote
Enclosure**
E1 ST T4 N/A 135°C N/A
E2 ST T4 N/A 135°C N/A
E3 ST T6 T4 85°C 135°C**
E4 ST T6 T4 85°C 135°C**
E3 HT T6 T1 85°C 450°C**
E4 HT T6 T1 85°C 450°C**
*Temperature code ratings for Zones are dependent on external process temperature factors and equipment enclosure
conguration. See the table above for specic temperature code ratings.
**The IECEx dust rating does not apply to the Remote Enclosure.
Specic Conditions of Use:
1. The ameproof joints of the equipment are not intended to be repaired. Consult the manufacturer
if dimensional information on the ameproof joints is necessary.
2. Refer to the manufacturer’s instructions to reduce the potential of an electrostatic charging hazard
on the equipment enclosure.
Appendix | 125