INSTALLATION OF THE OUTDOOR UNIT
Tools
Figure C.1 (Tools)
Verify with tool manufacturers that all tools used during servicing of the refrigerant are non-sparking and can be used with A2L Refrigerants.
No halide torches for leak testing.
Refrigerant monitors or detectors must be used to detect refrigerant in the work area.
R-454B A2L Refrigerant Recovery System.
Vacuum Pump rated for A2L refrigerant (capable of 300 microns or less vacuum.)
Nitrogen bottle with purging and pressurizing capabilities up to 550 psi.
Non-Sparking (Not Halide)Electronic Leak Detector rated for detecting A2L refrigerant.
Digital refrigerant scale Refrigeration Gauges rated for A2L Refrigerants with temp scales for R-454B refrigerant.
Gauge Manifold (Right handed threads).
A2L compatible Vacuum Gauge capable of 300 microns or less.
Nitrogen regulator for purging and testing, rated to 800 psi. (Capable of low psi flow)
Pipe tubing cutter.
Refrigerant recovery cylinder. (Flammable A2L label)
Ventilation fan.
Class ABC fire extinguisher.
Purge hose fittings
Flaring tool
Recovery Machine
Vaccum Pump
Nitrogen
ABC Fire Extinguisher
Guage Manifold
Nitrogen Regulator
Vacuum Guage