EasyManua.ls Logo

Froling T4 - Connecting the System; Connecting the Ash Discharge System to the TX; Connecting the Safety Switch on the Standard Dustbin to the TX

Froling T4
40 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
If the flexible tube on the gravity shaft is too long:
Loosen the hose clamps at the top and bottom and remove the hose
Cut to the required length
Reattach the tube using the hose clamps
4.7 Connecting the system
4.7.1 Connecting the ash discharge system to the TX
Insert the cables from the drive unit into the boiler controller
Connect the cables to the “Vibration motor (12)” output on the wood chip
module
From software version 50.04 – Build 05.10
4.7.2 Connecting the safety switch on the standard dustbin to the TX
NOTICE! Connect the safety switch cables to the terminals; see wood chip module
circuit diagram!
4
Assembly
Connecting the system
28 Fröling GesmbH | A-4710 Grieskirchen, Industriestraße 12 | www.froeling.com

Table of Contents

Related product manuals