If the flexible tube on the gravity shaft is too long:
❒ Loosen the hose clamps at the top and bottom and remove the hose
❒
Cut to the required length
❒ Reattach the tube using the hose clamps
4.7 Connecting the system
4.7.1 Connecting the ash discharge system to the TX
❒ Insert the cables from the drive unit into the boiler controller
❒ Connect the cables to the “Vibration motor (12)” output on the wood chip
module
➥ From software version 50.04 – Build 05.10
4.7.2 Connecting the safety switch on the standard dustbin to the TX
NOTICE! Connect the safety switch cables to the terminals; see wood chip module
circuit diagram!
4
Assembly
Connecting the system