Status codes and remedy
Display Status codes are displayed on the user interface of the inverter in the "System"
→ "Event Log" menu or in the user menu under "Notifications" or in Fronius Sol-
ar.web*.
* with corresponding configuration, see chapter Fronius Solar.web on page
15.
Status codes
1030 – WSD Open (operating LED: flashes red)
A device that is connected in the WSD chain has interrupted the sig-
nal line (e.g., surge protection device) or the bypass installed ex works
as standard has been removed and no trigger device has been in-
stalled.
If the SPD surge protection device has tripped, the inverter must be
repaired by an authorized specialist.
Install the bypass installed ex works as standard or a trigger device.
Turn the WSD (wired shutdown) switch to position 1 (WSD master).
WARNING!
Danger from work that is not carried out properly.
This can result in severe personal injury and damage to property.
▶
The installation and connection of an SPD surge protection device may only
be carried out by Fronius-trained service personnel in accordance with the
technical specifications.
▶
Observe safety rules.
Cause:
Remedy:
OR:
OR:
1173 – ArcContinuousFault (operating LED: flashes red)
An electric arc has been identified on the PV system, and the maxim-
um number of automatic connections within 24 hours has been
reached.
Keep the sensor pressed on the inverter for 3 seconds (max. 6
seconds).
On the user interface of the inverter, in the menu field "System" →
"Event Log", confirm the status "1173 – ArcContinuousFault".
On the user interface of the inverter, in the user menu "Messages",
confirm the status "1173 – ArcContinuousFault".
CAUTION!
Danger from damaged components of the PV system
This can result in severe personal injury/damage to property.
▶
Before the status "1173 – ArcContinuousFault" is confirmed, the entire PV
system affected must be checked for any possible damage.
▶
Damaged components must be repaired by qualified specialists.
Cause:
Remedy:
OR:
OR:
1191 – AfciDataTransfer (operating LED: flashes yellow)
An electric arc has been identified on the PV system.
No action required.
Cause:
Remedy: