Connection dia-
gram - 3 relays
The ripple control signal receiver and the I/O terminal of the inverter can be con-
nected to one another as shown in the connection diagram.
For distances of over 11 yd between the inverter and the ripple control signal re-
ceiver, a CAT 5 cable is recommended as a minimum and the shielding must be
connected on one side at the push-in terminal of the data communication area
(SHIELD).
(2)
IO4
V+
V+
IO0
IO2
IN6
IN8
IN10IN11
IN9
IN7
IO5
IO3
IO1
GND
GND
60 %
30 %
0 %
(1)
V+
IN8
IN9
IN10
(1) Ripple control signal receiver with 3 relays for effective power limitation.
(2) I/Os of the data communication area.
Use pre-configured file for 3-relay operation:
1
Download the file (.fpc) under 3-relay operation to the mobile device.
2
Upload the file (.fpc) in the "I/O power management" menu field by clicking
the "Import" button.
3
Click "Save".
The settings for 3-relay operation are saved.
91