Technical data
Technical data
for Fronius
Primo GEN24 7.7
208 - 240
DC input data
MPP voltage range 260 - 480 V
Max. input voltage
at 1000 W/m²/14 °F in an open circuit
600 V
Min. input voltage 65 V
Start-up input voltage 65 V
Nominal PV power at 208 V
at 220 V
at 240 V
7920 W
7920 W
7920 W
Nominal input voltage at 208 V
at 220 V
at 240 V
365 V
365 V
385 V
Max. PV array power at 208 V
at 220 V
at 240 V
11520 W
11520 W
11520 W
Nominal input current at 208 V
at 220 V
at 240 V
21.7 A
21.7 A
20.6 A
Max. input current
PV 1
PV 2
22 A
22 A
Max. short circuit current for module array (I
SC PV
)
PV 1
PV 2
41.25 A
36 A
Max. total short circuit current for module array
(I
SC PV1
+ I
SC PV2
= I
SC max
) 77.25 A
Max. continuous utility backfeed current
1)
0.0 A
AC output data
Max. output power at 208 V
at 220 V
at 240 V
7680 W
7680 W
7680 W
Max. output power at
+140 °F (60 °C) V min /
V max
at 208 V
at 220 V
at 240 V
7680 W
7680 W
7680 W
Nominal AC voltage 208 V/220 V/240 V
Voltage trip limit accuracy 1% of nominal value
Max. continuous output
current at V
nom
at 208 V
at 220 V
at 240 V
36.9 A
34.9 A
32.0 A
Output overcurrent pro-
tection
at 208 V
at 220 V
at 240 V
50.0 A
45.0 A
40.0 A
Phases 1
104