Knockouts
Preparing
knockouts for
connection
IMPORTANT! The knockouts must be drilled out using a step drill bit only. The
maximum conduit sizes are ½ - 1 inch / 13 - 25 mm.
IMPORTANT! Void warranty if the conduit holes are drilled improperly.
-
Use suitable eye protection when
drilling out the knockouts.
-
Avoid drilling too far to ensure the
connection area is not damaged.
-
When drilling out the knockouts at
the back, place the inverter on an
even surface with the back up-
wards so that shavings and pieces
of plastic can fall out of the invert-
er.
-
If necessary, deburr the knockouts
with a suitable tool and remove the
drilling residues from the inverter.
...sealant
permanently
elastic sealant
Conduit
fitting
Conduit
Inverter
housing
Conduit
Conduit
NOTE!
Condensation within the conduits can damage the inverter or components of
the photovoltaic systems.
To avoid undesirable air circulation and condensation in the conduits:
▶
Attach appropriate conduits to all knockouts that have been drilled open.
▶
When installing outdoors, only use waterproof conduit fittings and conduits.
▶
Seal the conduits in accordance with the pictures above on both sides.
NOTE!
Conduit fittings and conduits are not part of the scope of supply for the invert-
er.