Routing data
communication
cables
1
Drill out the knockout with a step drill.
2
Insert the conduit into the hole and fasten it using the torque specified by
the manufacturer. Seal the conduit as per the chapter headed Preparing
knockouts for connection on page 41.
3
Run the data communication cables
through the electrical installation tube
from below.
Terminating res-
istors
It may be possible for the system to function without terminating resistors.
However, owing to interference, the use of terminating resistors according to the
following overview is recommended for trouble-free operation.
For permissible cables and max. distances for the data communication area,
refer to the chapter headed Permitted cables for the data communication con-
nection on page 46.
IMPORTANT!Terminating resistors that are not positioned as illustrated can res-
ult in interference in the data communication.