EasyManua.ls Logo

Fronius Primo GEN24 208-240 - Remote Control and Cloud Integration

Fronius Primo GEN24 208-240
120 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
"Modbus port"
Number of the TCP port that is to be used for Modbus communication.
"SunSpec Model Type"
Depending on the SunSpec model, there are two different settings.
float: SunSpec Inverter Model 111, 112, 113 or 211, 212, 213 or 701, 702, 703,
704, 705, 706, 707, 708, 709, 710, 711, 712, 713
int + SF: SunSpec Inverter Model 101, 102, 103 or 201, 202, 203 or 701, 702,
703, 704, 705, 706, 707, 708, 709, 710, 711, 712, 713
"Meter address"
The value entered is the identification number (Unit ID) assigned to the
meter.Can be found on the user interface of the inverter in the “Communication
“Modbus” menu.
Factory setting: 200
"Meter address"
The value entered is the identification number (Unit ID) assigned to the meter.
Can be found on the user interface of the inverter in the “Communication
“Modbus” menu.
Factory setting: This value is invariably defined as 1.
Inverter control via Modbus
If this option is activated, the inverter is controlled via Modbus.
Inverter control includes the following functions:
-
on/off
-
Power reduction
-
Specification of a constant power factor (cos phi)
-
Specification of a constant reactive power value
Remote control
Remote control and Profiles
The grid operator/energy supplier can influence the output power of the inverter
via remote control. This requires the inverter to have an active Internet connec-
tion.
Parameter Value range Description
Remote control Off The remote control of the inverter is deac-
tivated.
On The remote control of the inverter is activ-
ated.
Allow remote
control for reg-
ulation pur-
poses (techni-
cian)
Deactivated/
Activated
The Allow remote control for regulation
purposes function may be mandatory for
proper operation of the system. *)
Allow remote
control for vir-
tual power
plants (custom-
er)
Deactivated/
Activated
If the Allow remote control for regulation
purposes function is activated (technician
access required), the Allow remote con-
trol for virtual power plants function is
automatically activated and cannot be de-
activated. *)
*) Cloud control
A virtual power plant is an interconnection of multiple generators to form a
group. This group can be controlled by means of the cloud control via the Inter-
84