EasyManua.ls Logo

Fronius Primo GEN24 208-240 - Page 57

Fronius Primo GEN24 208-240
120 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
5
Select the cable cross-section in ac-
cordance with the instructions in Per-
mitted cables for the electrical con-
nection from page 45.
Strip the insulation of the single con-
ductors by 0.47 inches. Lift to open
the terminal's operating lever and in-
sert the stripped single conductor into
the slot provided in the terminal as far
as it will go.
Then close the terminal's operating
lever until it engages.
* For double-insulated cables, observe
the max. cross-section of the insula-
tion.
WARNING!
Danger from loose and/or incorrectly
clamped single conductors in the ter-
minal.
This can result in severe personal in-
jury and damage to property.
Only connect one single conductor
at each slot provided in the ter-
minal.
Check that the single conductors
are secure in the terminal.
Make sure that the single conduct-
or has been fully inserted into the
terminal and that no single wires
are protruding out of the terminal.
6
57

Table of Contents

Other manuals for Fronius Primo GEN24 208-240

Related product manuals