Parameter Value range Description
"Inverter shut-
down before 30
mA FI triggers"
0 No measures to prevent false alarms.
1 The inverter shuts down at 15 mA, before
the residual current circuit breaker is
triggered.
"Leakage cur-
rent factor for
reducing
RCMU/FI false
alarms"
0 0.25
(default: 0.16)
By reducing the set value, the leakage cur-
rent is reduced and the intermediate cir-
cuit voltage is increased, which slightly
lowers the efficiency. A set value of 0.16
ensures optimum efficiency.
"Insulation warning"
Parameter Value range Description
"Insulation
warning"
Off The insulation warning is deactivated.
On The insulation warning is activated.
A warning is output in the event of an insu-
lation fault.
"Insulation
measurement
mode"
Exact Insulation monitoring takes place with the
highest degree of accuracy and the meas-
ured insulation resistance is displayed on
the user interface of the inverter.
Fast Insulation monitoring takes place with a
lesser degree of accuracy, whereby the
time to take the insulation measurement is
shortened and the insulation value is not
displayed on the user interface of the in-
verter.
"Threshold for
the insulation
warning"
100000
10000000
If the value drops below the threshold,
status code 1083 is displayed on the user
interface of the inverter.
"Backup power"
Parameter Value range Description
"Backup power
nominal
voltage"
220 240 V The nominal phase voltage that is output
in backup power mode.
"Backup power
undervoltage
protection limit
value U< [pu]"
0 2 % V This set value represents the limit value
for shutting down backup power mode.
e. g., set value 0.9 = 90 % of the nominal
voltage.
"Backup power
undervoltage
protection time
U<"
0.04 20 s Trip time for falling below the backup
power undervoltage protection limit value.
"Backup power
surge protec-
tion limit value
U> [pu]"
0 2 % V This set value represents the limit value
for shutting down backup power mode.
e. g., set value 1.1 = 110 % of the nominal
voltage.
"Backup power
surge protec-
tion time U>"
0.04 20 s Trip time for exceeding the backup power
surge protection limit value.
76