Calibrating the
empty state
Drain the parting agent container until
the parting agent level is at least 20
mm (0.787 in.) below the sensor
Establish a power supply to the sensor
Press the "OUT OFF" button for bet-
ween 2 and 6 seconds
- The LED on the sensor flashes
slowly
- After releasing the "OUT OFF"
button the LED goes out - the sen-
sor has detected a low fluid level
Calibrating the
full state
Fill the parting agent container with
parting agent
20 mm (0.79 in.)
1
2
2 - 6 s
3
1