The following settings are available for temperature-controlled charging:
automatic/OFF/required
-
automatic ... Temperature-dependent adjustment of the charging character-
istic.
-
OFF ... The measured battery temperature is not taken into account.
-
required ...
Charging only starts if the temperature sensor is connected.
Error overtemperature ON/OFF
-
ON ... Error message in the event of battery overtemperature.
Charging process stops and can only be continued once the battery has
cooled down and been reconnected.
-
OFF ... No error message in the event of battery overtemperature.
Warning overtemperature ON/OFF
-
ON ... Warning in the event of battery overtemperature.
-
OFF ... No warning in the event of battery overtemperature.
An external temperature sensor is required for certain characteristics. If this
type of characteristic is selected in configuration mode, a note is shown indicat-
ing that an external temperature sensor is required.
The following characteristics require an external temperature sensor:
-
28 - FCC IUI - CSM WET
-
30 - FCC IUI - WET
A note is displayed if a characteristic
that requires an external temperature
sensor is selected.
1
Use the "Pause/Start" key to con-
firm the note.
Equalising
charge
Equalising charge
OFF
-
There is no equalising charge.