mixing of the electrolyte to take place. The benefit is the reduced heating of the
battery, and consequently longer battery-life, plus reduced water loss during
charging.
If a pump fault or leaks in the connection with the battery result in a fault being
detected, then the status code "Statecode 14" will appear on the display. One
way in which this fault can be indicated is by using an external indicator lamp to
show a common error.
Weight of the electrolyte circulation set:
Air-Puls + air hose kit
3 kW 2.5 kg (5.51 lb)
Electrolyte circulation air filter insert
The air filter insert for the integrated air pump should be cleaned once a year. In
dusty environments, the cleaning interval should be shortened accordingly. The
air filter insert must be removed for cleaning. Remove the air filter by levering it
out with a slotted screwdriver; then refit it as follows:
NOTE!
Danger from using the air filter with unsuitable chargers.
This can result in damage to property.
Only use the air filter with the chargers provided by the manufacturer for
this purpose.
57
EN

Table of Contents

Other manuals for Fronius Selectiva 3.0

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fronius Selectiva 3.0 and is the answer not in the manual?

Fronius Selectiva 3.0 Specifications

General IconGeneral
BrandFronius
ModelSelectiva 3.0
CategoryBattery Charger
LanguageEnglish

Related product manuals