3.6 Other Precautions
For using a multi-function keypad note that your key operation will be differed from ones on a standard keypad
(TP-E1) for following points.
3.6.1 Function code setting for F02 (Run and operation)
The
/ key controls to run/stop the motor on the standard keypad (TP-E1) while the rotation command
input is required. On the contrary, the
/ /
key on the multi-function keypad controls to run
forward/reverse the motor without inputting any rotation command or stop it.
The function code F02 specifies the run command source to drive the motor.
F02 data Run command source
0: Keypad
Pressing the
/ / key runs/stops the motor.
1: Digital input The terminal command (FWD) or (REV) runs/stops the motor.
2: Keypad (Forward)
The
/ key runs the motor forward or stops it, but does not run it
reverse.
3: Keypad (Reverse)
The
/
key runs the motor reverse or stops it, but does not run it
forward.
If you select Local by the Remote/Local switching command, operation of the run command from the keypad will
be changed by setting of the function code F02.
For details, refer to “ Switching the operation mode between remote and local” in “3.3.1
Running/stopping the motor.
3.6.2 Remote/local operation
The multi-function keypad features the
key to switch the operation between remote and local modes.
For details, refer to “ Switching the operation mode between remote and local” in “3.3.1
Running/stopping the motor.