3-46
3.6.3 Tuning motor parameters
The LCD monitor of multi-function keypad shows the lead-through screen for tuning of motor parameters. To
tune motor parameters follow screens below.
Entering into tuning motor parameters
Set data 1 or 2 into the function code P04 and press the
key.
Waiting for a run command.
Tuning the motor parameters. (Note 2)
(Note 1) The factory default setting is “Run forward” by using the key on the keypad. To tune the motor parameters
in “Run reverse”, change data of the function code F02.
(Note 2) • Time needed for tuning while the motor is stopped (P04 = 1) will be less than 40 seconds.
• In tuning while the motor is running (P04 = 2), the inverter accelerates the motor up to around 50% of the
base frequency, starts tuning of motor parameters, and decelerates to stop the motor after the end of tuning.
Estimated time needed for tuning in this case will be (acceleration time + 10 + deceleration time) seconds.
Press
/
key to select the data either 1 or 2 being set
to the function code P04.
/
Press
key to select the tuning mode.
Turn on the
run command.
Give the specific run command, Run forward or Run
reverse. (Note 1)
End of tuning
Upon turning off the run command (while the run
command given by the keypad or the link operation is
automatically turned off) the lead-through ends the
tuning process, and moves to the next function code
P06.
Turn off the
run command.