5-45
F34
F35
Terminal [FMI] (Output Adjustment)
(Function)
For [FMI]
The inverter outputs monitoring data including output frequency and output current via terminal
[FMI] in analog current level.
Output adjustment (F34)
Setting this function code adjusts the output current level of the selected monitor item within 0 to
200% as well as the function code F30.
Function (F35)
Setting this function code selects a monitor item to be output to terminal [FMI] as well as the
function code F31.
E01 to E05
E98, E99
Command Assignment to [X1] to [X5]
Command Assignment to [FWD] and [REV]
Function codes E01 to E05, E98 and E99 allow you to assign commands to terminals [X1] to [X5],
[FWD], and [REV] which are general-purpose, programmable input terminals.
These function codes may also switch the logic system between normal and negative to define
how the inverter logic interprets either ON or OFF status of each terminal. The default setting is
normal logic system "Active ON." So, explanations that follow are given in normal logic system
"Active ON."
In the case of digital input, you can assign commands to the switching means for the run command
and its operation, the reference frequency and the motor drive power (e.g., (SS1), (SS2), (SS4),
(Hz2/Hz1), (SW50), (SW60), (Hz/PID), (IVS), (LE), (LOC), and (FR2/FR1)). Be aware of that
switching of any of such signals may cause a sudden start (running) or an abrupt change in speed.
An accident or physical injury may result.