5-44
Output adjustment (F30)
F30 allows you to adjust the output voltage or current representing the monitored data selected
by function code F31 within the range of 0 to 200%.
Function (F31)
F31 specifies what is output to the analog output terminal [FMA].
Data for F31 [FMA] output
Function
(Monitor the following)
Meter scale
(Full scale at 100%)
0
Output
frequency
Output frequency of the
inverter
Maximum frequency (F03)
2
Output current
Output current (RMS) of
the inverter
Twice the inverter rated current
3
Output voltage
Output voltage (RMS) of
the inverter
250 V for 200 V series,
500 V for 400 V series
4
Output torque Motor shaft torque Twice the rated motor torque
5
Load factor
Load factor (Equivalent
to the indication of the
load meter)
Twice the rated motor load, or
Rated output torque of the
motor at the base frequency
or below
Rated motor output (kW) at
the base frequency or above
6
Input power
Input power of the
inverter
Twice the rated output of the
inverter
7
PID feedback
value (PV)
Feedback value under
PID control
100% of the feedback value
9
DC link bus
voltage
DC link bus voltage of
the inverter
500 V for 200 V series,
1000 V for 400 V series
10
Universal AO
Command via
communications link
(Refer to the RS-485
Communications User’s
Manual)
20,000 as 100%
13
Motor output Motor output (kW) Twice the rated motor output
14
Calibration
analog output
(+)
Full scale output of the
meter calibration
10 VDC or 20 mA DC
15
PID process
command (SV)
Process command
under PID control
100% of the feedback value
16
PID process
output (MV)
Output level of the PID
controller under PID
control (Frequency
command)
Maximum frequency (F03)