5-44
Output adjustment (F30)
F30 allows you to adjust the output voltage or current representing the monitored data selected
by function code F31 within the range of 0 to 200%.
Function (F31)
F31 specifies what is output to the analog output terminal [FMA].
Data for F31 [FMA] output
Function
(Monitor the following)
Meter scale
(Full scale at 100%)
0
Output
frequency
Output frequency of the
inverter
Maximum frequency (F03)
2
Output current
Output current (RMS) of
the inverter
Twice the inverter rated current
3
Output voltage
Output voltage (RMS) of
the inverter
250 V for 200 V series,
500 V for 400 V series
4
Output torque Motor shaft torque Twice the rated motor torque
5
Load factor
Load factor (Equivalent
to the indication of the
load meter)
Twice the rated motor load, or
• Rated output torque of the
motor at the base frequency
or below
• Rated motor output (kW) at
the base frequency or above
6
Input power
Input power of the
inverter
Twice the rated output of the
inverter
7
PID feedback
value (PV)
Feedback value under
PID control
100% of the feedback value
9
DC link bus
voltage
DC link bus voltage of
the inverter
500 V for 200 V series,
1000 V for 400 V series
10
Universal AO
Command via
communications link
(Refer to the RS-485
Communications User’s
Manual)
20,000 as 100%
13
Motor output Motor output (kW) Twice the rated motor output
14
Calibration
analog output
(+)
Full scale output of the
meter calibration
10 VDC or 20 mA DC
15
PID process
command (SV)
Process command
under PID control
100% of the feedback value
16
PID process
output (MV)
Output level of the PID
controller under PID
control (Frequency
command)
Maximum frequency (F03)