10-9
FRN250F1S-4U to FRN350F1S-4U
1) Remove the front cover. Refer to Chapter 2, Section 2.3 "Wiring."
2) Change wiring at points A and B shown in the internal location diagram below.
Figure 10.10 Internal Location Diagram (FRN250F1S-4U to FRN350F1S-4U)
Point A As shown below, remove the screw (M4) to release the wire end terminal and secure the terminal
to the support with the screw removed. (Tightening torque: 15.9lb-in(1.8 N·m))
Figure 10.11 Point A
Point B As shown below, cut the cable tie (insulation lock) with a nipper to remove the protective cap.
Remove the screw (M5) and secure the wire end terminal with the screw removed. (Tightening torque:
31.0lb-in(3.5 N·m))
Figure 10.12 Point B