5-58
Inverter output on -- (RUN2)
(Function code data = 35)
This output signal comes ON when the inverter is running at the starting frequency or below or the
DC braking is in operation.
Overload prevention control -- (OLP)
(Function code data = 36)
This output signal comes ON when the overload prevention control is activated. The minimum
ON-duration is 100 ms.
For details of the overload prevention control, refer to the descriptions of function code H70.
Current detected -- (ID)
(Function code data = 37)
This output signal comes ON when the output current of the inverter exceeds the level specified
by E34 (Current detection (Level)) for the time longer than the one specified by E35 (Current
detection (Timer)). The minimum ON-duration is 100 ms.
This signal goes OFF when the output current drops below 90% of the rated operation level.
Function code E34 is effective for not only the motor overload early warning (OL), but
also for the operation level of the current detection (ID).
For details of the current detection, refer to the descriptions of function codes E34 and E35.
Low output torque detected -- (U-TL)
(Function code data = 45)
This output signal comes ON when the torque value calculated by the inverter decreases below
the level specified by E80 (Detect low torque (Detection level)) for the time longer than the one
specified by E81 (Detect low torque (Timer)). The minimum ON-duration is 100 ms.
For details of the low output torque detection, refer to the description of function codes E80
and E81.
Inverter in remote operation -- (RMT)
(Function code data = 54)
This output signal comes ON when the inverter switches from local to remote mode.
For details about the remote and local modes, refer to Chapter 3, Section 3.3.1 "■
Switching the operation mode between remote and local."
Terminal C1 off signal -- (C1OFF)
This output signal comes ON when the input current of terminal [C1] is less than 2mA, and
goes OFF when it is 2mA or more.
Alarm output (for any alarm) -- (ALM)
(Function code data = 99)
This output signal comes ON if any of the protective functions is activated and the inverter enters
Alarm mode.