2-29
Table 2.10 Continued
Classifi-
cation
Symbol Name Functions
[FMA] Analog
monitor
The monitor signal for analog DC voltage (0 to +10 V) or analog DC current (+4 to +20
mA) is output. You can select either one of the output switching the slide switch SW4 on
the control PCB (Refer to Section 2.3.8.), and changing data of the function code F29.
You can select one of the following signal functions with function code F31.
Output frequency Output current Output voltage
Output torque Load factor Input power
PID feedback value DC link bus voltage Universal AO
Motor output Analog output test PID command
PID output
* Input impedance of the external device: Min. 5kΩ (0 to 10 VDC output)
Input impedance of the external device: Max. 500Ω (4 to 20 mA DC output)
* While the terminal is outputting 0 to 10 VDC, an output less than 0.3 V may become 0.0
V.
* While the terminal is outputting 0 to 10 VDC, it is capable of driving up to two meters
with 10 kΩ impedance. While outputting the current, to drive a meter with 500 Ω
impedance max. (Adjustable range of the gain: 0 to 200%)
[FMI] Analog
monitor
The monitor signal for analog DC current (+4 to +20 mA) is output. You can select one of
the following signal functions with function code F35.
Output frequency Output current Output voltage
Output torque Load factor Input power
PID feedback value DC link bus voltage Universal AO
Motor output Analog output test PID command
PID output
* Input impedance of the external device: Max. 500Ω
* It is capable of driving a meter with a maximum of 500Ω impedance.
(Adjustable gain range: 0 to 200%)
Analog output
[11] Analog
common
Two common terminals for analog input and output signal terminals
These terminals are electrically isolated from terminals [CM]s and [CMY].