To help with power cord management and prevent incorrect connections, attach labels to the power cords
and make a note of connection origins and destinations.
1 Remove the power cord clamp from the power distribution unit.
Loosen the two thumb screws on both sides of the power cord clamp to remove it.
Power cord clamp
Thumb screw
2 Connect the power distribution unit outlets and power supply unit inlets with the power cords (AC out-
put cables).
The procedures to connect the power supply unit is same as Step 1 in "4.4.1 When No Power Distribu-
tion Units are Installed" (page 50).
Connect the PSU#0 power cord to power distribution unit#0 (the lower power distribution unit). Con-
nect the PSU#1 power cord to power distribution unit#1 (the higher power distribution unit).
The following figures show a connection diagram of AC outlet cables.
OUT 1
OUT 2
OUT 3
OUT 4
OUT 5
OUT 6
OUT 1
OUT 2
OUT 3
OUT 4
OUT 5
OUT 6
Drive enclosure 1
Controller enclosure
Power distribution unit #1
Power distribution unit #0
PSU#1 InletPSU#0 Inlet
PSU#1 InletPSU#0 Inlet
:
Connect OUTPUT#0-n of the Power distribution unit to the PSU#0 inlet of the ETERNUS DX.
:
Connect OUTPUT#1-n of the Power distribution unit to the PSU#1 inlet of the ETERNUS DX.
Chapter 4 Connecting Cables
4.4 Power Cord Connection
53
FUJITSU Storage ETERNUS DX60 S3 Disk storage system
Configuration Guide (Basic)
Copyright 2014 FUJITSU LIMITED
P3AM-9002-01ENZ0