2 Connect the power distribution unit outlets and power supply unit inlets with the power cords (AC out-
put cables).
The procedures to connect the power supply unit is same as Step 1 in "4.4.1 When No Power Distribu-
tion Units are Installed" (page 50).
The following figure shows an example of AC output cable connection:
Drive enclosure 1
Controller enclosure
: Connect
OUTPUT#0-n of the Power distribution unit to the PSU#0 inlet of the ETERNUS DX.
: Connect
OUTPUT#1-n of the Power distribution unit to the PSU#1 inlet of the ETERNUS DX.
Power distribution unit
Outlet
OUTPUT #0-1
Outlet
OUTPUT #0-2
Outlet
OUTPUT #1-2
Outlet
OUTPUT #1-1
PSU#1 Inlet
PSU#1
Inlet
PSU#0
Inlet
PSU#0 Inlet
3 Connect the power cord (AC input cable) plugs to the inlets of the power distribution unit.
Inlet
INPUT #0
Inlet
INPUT #1
Power distribution unit
4 Use the power cord clamps to prevent the power plugs from coming unplugged.
Attach the power cord clamps removed in Step 1.
5 Connect the plugs on the other end of the power cords (AC input cables) that were connected in Step 3
to the sockets.
Power supply failure can be prevented by connecting the power cords (AC input cables) on the IN-
PUT#0 side and the INPUT#1 side to different power sources.
4.4.3 When 2U Power Distribution Unit is Installed (for Regions Other than EMEA&I)
The following procedure explains how to connect the power cords when a 2U power distribution unit (12 out-
let type or 16 outlet type) is installed.
This section explains how to install a 12 outlet type power distribution unit as an example. This installa-
tion method can also be applied to a 16 outlet type power distribution unit.