e.bloxx A6-2CF
MOUNTING E.BLOXX AND CONNECTING WIRES
20
HB_EBLOXX-A62CF_E_V19.doc
Gantner Instruments Test & Measurement GmbH
Notice:
The current flowing through the Rapid Bus Link Plug Jack and the e.bloxx must not exceed 1 A. Thus, the
power supply should preferably be connected to the middle of several modules and no more than 5 pieces of
e.bloxx may be connected via the Rapid Bus Link Plug ICM 100 in one line. So the supply should be
connected to the module in the middle and 2 further modules could be connected on the left and 2 modules
on the right side
B
U-
Profile Rail 35 mm (1.4 inch) Rapid Bus Link Plugs ICM 100
U+
Picture 3.11.
- Connection of four e.bloxx Modules with Rapid Bus Link Plugs ICM 100