EasyManua.ls Logo

Gantner e Series - Alarm

Gantner e Series
78 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
e.bloxx A6-2CF
CONFIGURATION
HB_EBLOXX-A62CF_E_V19.doc
65
Gantner Instruments Test & Measurement GmbH
5.4.5 Alarm
To protect men and machine it is necessary to set alarm levels. Will a level be reached by one of a conditioned signals a
alarm signal will be generated. The output of an alarmc channel is the digital state 0 or 1. This can be read by the host
or can be used for further conditioning like boolean algebra (e.g. if alarm 1 and alarm 2 and alarm 3 than set V6). For
the response time to detect a alarm the same rule like for the artihmitc functions are valid. That means the time depens
on the number of taken number of variables. The minimum time is 1 ms, tha maximum time wil be approx. 20 ms.
To set an alarm it is necessary to define a new variable. For that option click at any field in a row.
Column "Type"
Select
Alarm
in the window that opens when clicking on that column.
Columns "Variable Name" and "Format/Adjustment"
According to chapter
5.4.2 Signal Conditioning
.
Columns "Sensor", "Type of", "Connection" and "Terminals"
These columns are not relevant for the signal conditioning.
Column "Additionals"
In this column it is possible to set limit switches/thresholds. There are up to 4 thresholds each alarm channel possible.
The result will be a logical OR combination of all 4 thresholds.
The thresholds provide the function to compare a variable with another variable or with a constant. The variable could
be a measured value, a conditioned value or a value set by host (setpoint).

Table of Contents

Related product manuals