4–20 339 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL
A3 RECORDS CHAPTER 4: ACTUAL VALUES
Learned data recorder
The Learned Data Recorder measures and records up to 250 data record "sets," as
indicated in the Learned Data section above, all from actual motor operation. This data can
be used to evaluate changes/trends over time. Note that learned values are calculated
even when features requiring them are turned off.
Clearing motor data (ACTUAL VALUES > A3 RECORDS > CLEAR LEARNED DATA) resets all
these values to their default settings.
LEARNED DATA REC
Range: #xxxx1 of xx250 in steps of 1
This value indicates the number of learned data records saved to date. Only the latest
250 records can be viewed.
DATE OF RECORD
Range: Month, Day, Year
This value is the date on which the record was saved.
Clear learned data
CLEAR LEARNED DATA
No
Range: No, Yes
When set to "Yes," pressing the ENTER key will clear all learned data.
Clear event record
PATH: ACTUAL VALUES > A3 RECORDS > CLEAR EVENT REC
CLEAR
No
Range: No, Yes
When set to "Yes," pressing the ENTER key will clear all event records.
Clear transient record
PATH: ACTUAL VALUES > A3 RECORDS > CLEAR TRANST REC
CLEAR
No
Range: No, Yes
When set to "Yes," pressing the ENTER key will clear all transient records.
Clear fault report
PATH: ACTUAL VALUES > A3 RECORDS > CLEAR FAULT REPORT
CLEAR
No
Range: No, Yes
When set to "Yes," pressing the ENTER key will clear all fault reports.