EasyManua.ls Logo

GE 339

GE 339
342 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6–24 339 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL
S2 SYSTEM SETUP CHAPTER 6: SETPOINTS
S2 System Setup
Figure 6-11: Main system setup menu
Current sensing
PATH: SETPOINTS > S2 SYSTEM SETUP > CURRENT SENSING
NOTE
NOTE:
The CT secondary value of 1 or 5 A must be specified at the time of order so that the proper
hardware is installed.
NOTE
NOTE:
The setting GROUND CT PRIMARY is seen only if the GROUND CT TYPE is set to “1A
Secondary” or “5A Secondary”.
PHASE CT PRIMARY
Range: 10 to 5000 A in steps of 1 A
Default: 100 A
The phase CT should be chosen so that the FLA is no less than 50% of the rated phase CT
primary. Ideally, the phase CT primary should be chosen so that the FLA is 100% of the
phase CT primary or slightly less; never more.
PHASE CT SECONDARY
Range: 1 A or 5 A
Default: 5 A
Configurable 1 A or 5 A secondary, available with Phase Current option ‘P0’ installed.
Enter the rated phase CT secondary current of the three-phase current transformers.
S2 SYSTEM SETUP
CURRENT SENSING
VOLTAGE SENSING
POWER SYSTEM
MOTOR
SWITCHING DEVICE
FLEXCURVE A
FLEXCURVE B
VFD
896765A4.cdr

Table of Contents

Related product manuals