6–174 339 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL
S6 MONITORING CHAPTER 6: SETPOINTS
Figure 6-83: Real Power Demand logic diagram
Reactive Power The Reactive Power Demand is monitored by comparing to a Pickup value. If the Reactive
Power Demand Pickup is ever equalled or exceeded, the relay can be configured to cause
an alarm or signal an output relay.
LED: PICKUP
Real Power Inputs
AN D
SETPOINTS
REAL PWR DEMAND
FUNCTION :
Disabled
Alarm
Latched Alarm
OR
SETPOINTS
REAL PWR DEMAND
MEASUREMENT TYPE :
Calculate Real Power
Demand
SETPOINTS
REAL PWR DEMAND
REAL POWER PICKUP :
|P Demand | ≥PICKUP
RUN
RealPwr Dmd PKP
AND AN D
Command
RESET
OR
LED: ALARM
REAL PWR DEMAND
THERMAL 90%
RESPONSE TIME :
REAL PWR DEMAND
TIME INTERVAL :
Three-Phase
Real Power (P)
FlexLogic Operands
S
LATCH
Set-
Dominant
R
SETPOINT
Do Not Operate, Operate
OUTPUT RELAY X
SETPOINTS
BLOCK 1:
Off = 0
BLOCK 2:
Off = 0
BLOCK 3:
Off = 0
OR
898847A1.CDR