EasyManua.ls Logo

GE 339

GE 339
342 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
CHAPTER 6: SETPOINTS S1 RELAY SETUP
339 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL 6–17
TRIGGER ON PKP
Range: Off, On
Default: Off
Selection of “Yes” setting enables triggering for the recorder upon Pickup condition
detected from any protection or control element.
TRIGGER ON DPO
Range: Off, On
Default: Off
Selection of “Yes” setting enables triggering for the recorder upon a Dropout condition
detected from any protection or control element.
TRIGGER ON TRIP
Range: Off, On
Default: Off
Selection of “Yes” setting enables triggering for the recorder upon Trip condition
detected from any protection or control element.
TRIGGER ON ALARM
Range: Off, On
Default: Off
Selection of “Yes” setting enables triggering for the recorder upon Alarm condition
detected from any protection or control element.
TRIGGER ON INPUT 1 to 3
Range: Off, Contact Input 1 to 10, Virtual Input 1 to 32, Remote Input 1 to 32, Logic
Element 1 to 16, CT Fail Alarm PKP, CT Fail Alarm OP
Default: Off
Selection of input or logic element from the settings range enables triggering input for
the recorder. A record will be triggered if the status of the selected input changes to “On”.
TRIGGER ON INPUT 1 to 3
Range: Off, Contact Input 1 to 10, Virtual Input 1 to 32, Remote Input 1 to 32, Logic
Element 1 to 16
Default: Off
Selection of input or logic element from the settings range enables triggering input for
the recorder. A record will be triggered if the status of the selected input changes to “On”.

Table of Contents

Related product manuals