CHAPTER 6: SETPOINTS S3 PROTECTION
339 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL 6–55
Figure 6-23: Undercurrent logic diagram
896808A1.CDR
S3 UNDERCURRENT
MOTOR STATUS
Stopped
AND
IA_mag < PICKUP
S3 UNDERCURRENT
U/CURR TRIP PKP
RUN
IB_mag < PICKUP
IC_mag < PICKUP
IA_mag < PICKUP
S3 UNDERCURRENT
U/CURR ALARM PKP
RUN
IB_mag < PICKUP
IC_mag < PICKUP
OR
OR
S3 UNDERCURRENT
U/CURR ALARM DELAY
t
PKP
0
LOGIC OPERAND
U/CURR TRIP OP
ANY TRIP OP
S3 UNDERCURRENT
U/CURR TRIP DLY
t
PKP
0
LOGIC OPERAND
U/CURR ALARM OP
ANY ALARM OP
S
R
LATCH
AND
AND
S3 UNDERCURRENT
U/CURR TRIP FUNC
DISABLED = 0
S3 UNDERCURRENT
BLK U/C ON START
t
BLK
0
BLOCK 1
BLOCK 2
BLOCK 3
OFF = 0
OFF = 0
OFF = 0
OR
S3 UNDERCURRENT
U/CURR ALARM FUNC
ENABLED = 1
IA
ACTUAL VALUE
IB
IC
Running
S2 MOTOR
ENABLE 2-SPD MOTOR
DISABLED = 0
MOTOR SPEED INDICATION
LOW SPEED
OR
AND
U/CURR TRIP PKP
U/CURR ALARM PKP
SETTINGS
SETTINGS
SETTINGS
SETTING
SETTINGS
SETTINGS
SETTING
SETTINGS
SETTINGS
TARGET MESSAGE
Undercurrent Alarm
State: Operate
Undercurrent Alarm
State: Pickup
TARGET MESSAGE
Undercurrent Trip
State: Operate
Undercurrent Trip
State: Pickup
OR
AND
AND
INPUTS
Emergency Restart Input
Lockout Reset Input
SETTINGS
Off = 0
Lockout Reset
Off = 0
Emergency Restart
S4 CONTROLS
ANY ALARM PKP
ANY TRIP PKP
KEYPAD RESET
AND
Reset Input
Reset
Off = 0
DISABLED = 0
SETTING
OUTPUT RELAY X
Do Not Operate, Operate